英文版的闭式水系统调试作业指导书
1 Objective
1.1 In order to instruct and control the commission work of system and equipments so as to guarantee the system and equipment can be put into operation safety and normally, this commissioning procedure is prepared.
1.2 Check the Electrical, C& I signal devices and interlock protection according to this commissioning procedure and make sure the indication is correct and action is reliable.
1.3 Check the running condition of the equipment and system according to this commissioning procedures, check the performance of the system so that the possible defectives can be removed.
1.4 This procedure is an introduction document. Commission engineer can modify the contents, which are not proper for site situation. As long as the commission purpose is reached and function at performance of turbine generator unit is checked to meet the requirement of design and operation, then all reasonable test, check, measure and operation method and steps are allowed.
2 Description to system and main equipment technical specification
Closed circulation cooling water pump
Type: KQSN300-N13/303
Flow: 550t/h
Head: 40m
Motor power: 55KW
Voltage: 400V
3 Commission range
Closed circulation cooling water system consists of closed water expansion
tank, closed water pump, turbine side water-water exchanger, coolers, valves, indication instruments of closed circulation cooling water. Water source is provided by chemical water or condensate water. The primary cooling water of closed circulation cooling water system adopts chemical DM water, secondary