TechTopics No. 09We are often asked to provide estimated heat generation data for our equipment. This issue of TechTopics provides information that allows calculation of approximate heat generated by the type GM38 switchgear under assumed loading conditions. The heat generation data given in the table is based on full-rated continuous current. Actual heat generation calculations must take into account the true loading of the equipment. The amount of heat generated is related to the square of the current, so a circuit breaker operating at one-half rated current will have heat generation only one-quarter of that at full-rated continuous current. Because the effect of the square relationship is very significant, it is overly conservative to estimate heat generation based on the assumption that all sections and all circuit breakers each carry their rated continuous current at all times. Air conditioning systems sized based upon such estimates will be much larger than the real operating conditions will require.

Table 1: Approximate full load heat generation (in watts (W)) for type GM38 switchgear (up to 38 kV)

Continuous current - circuit breaker (rows 1-3) or main bus (row 4) Rated current Category Actual current Circuit breaker cell with circuit breaker Vertical section with main bus Space heaters per vertical section Voltage transformer (VT) stationary Control power transformer (CPT) (stationary) Relaying and instrumentation per circuit breaker cell Microprocessor type Electromechanical non-complex Electromechanical complex1,200 A 461 W 211 W 1,000 W 250 W 4% of CPT kVA rating 50 W 100 W 200 W to 300 W 2,000 A 738 W 275 W 1,000 W 250 W 4% of CPT kVA rating 50 W 100 W 200 W to 300 W 3,000 A 1,443 W 452 W 1,000 W 250 W 4% of CPT kVA rating 50 W 100 W 200 W to 300 W 1,200 A 2,000 A 3,000 A

Heat generation estimation for type GM38 switchgear (up to 38 kV)

Answers for energy.

Notes on assumptions:

Space heaters, when provided, are not 1.

normally controlled by a thermostat. Hence, their load is represented as a continuous load. The purpose of space heaters is to prevent condensation, and this is not limited by the absolute temperature. Even when a thermostat is used to control the heaters, it is set to shut the heaters off at a

temperature of approximately 110º F.Therefore, in an air-conditioned room, the heaters would be energized continuously.Heat generated by current 2.

transformers is ignored as it is usually insignificant and varies according to the CT ratio as well as the loading.The CPT heat generation estimate is 3.

very conservative and assumes the CPT is operated at full-rated capacity. If normal loading is at less than full rating, heat generation may be

adjusted by the square of the percent loading.Relaying and instrumentation heat 4.

generation estimates are very approximate and are normally

estimated on the basis of the number of circuit breaker cells. Extensive relaying and instrumentation may

warrant additional conservatism in the estimation of associated heat generation.Conversion factor: watts x 3.415179 = 5.

BTU/hour.

Table 2: Calculations

To estimate the heat generated under actual loading conditions, determine the component heat generation for each of the components indicated in Table 1. Estimated heat generation for circuit breakers should be adjusted for actual loading based on the ratio of the squares of the actual current and the rated current.

To be precise, this adjustment should also be made for the actual current loading of the main bus for each individual vertical section, but this is frequently ignored in the interest of simplification. Instead, the main circuit breaker loading is usually assumed to be equal to the main bus loading in all vertical sections.

Example: Assume a lineup with five vertical sections, one 2,000 A main

circuit breaker (loaded to 1,650 A), three 1,200 A feeder circuit breakers (loading 850 A, 200 A and 600 A), 2,000 A main bus and space heaters. The lineup

includes one set of VTs, one 15 kVA CPT and microprocessor relaying, and

instrumentation. The calculations would be as described in Table 2.

If true loading were not considered (for example, all calculations performed on the basis of full-rated current), the calculations would yield a heat generation of 9,546 W.

For more information, please contact your local Siemens representative.

Published by and copyright © 2009:Siemens AGEnergy Sector

Freyeslebenstrasse 1

91058 Erlangen, Germany

Siemens Energy, Inc. 7000 Siemens Road

Wendell, North Carolina 27591 USA

For more information, contact +1 (800) 347-6659

http:///energy

Siemens Energy, Inc.

Order No. E50001-E710-A162-X-4A00

All rights reserved.

Trademarks mentioned in this document are the property of Siemens AG, its affiliates or their respective owners.

Subject to change without prior notice. The information in this document contains general descriptions of the technical options available, which may not apply in all cases.

The required technical options should therefore

be specified in the contract.

http:///energy

Siemens design guide TechTopics09.doc 将本文的Word文档下载到电脑,方便复制、编辑、收藏和打印
    ×
    二维码
    × 游客快捷下载通道(下载后可以自由复制和排版)
    VIP包月下载
    特价:29 元/月 原价:99元
    低至 0.3 元/份 每月下载150
    全站内容免费自由复制
    VIP包月下载
    特价:29 元/月 原价:99元
    低至 0.3 元/份 每月下载150
    全站内容免费自由复制
    注:下载文档有可能出现无法下载或内容有问题,请联系客服协助您处理。
    × 常见问题(客服时间:周一到周五 9:30-18:00)